Sizing Transformers for Variable Frequency Drive (VFD) Loads and Harmonic Currents

Variable frequency drives (VFD) are cutting-edge devices used in a drive system consisting of three main sub-systems: AC motor, main drive controller assembly and drive-operator interface. The units can also be used to control motor speeds, resulting in reduced energy consumption and preserved lifespans for connected machines.

To improve drive performance and reduce the creation of harmonic currents, VFDs can be protected by an isolation transformer. In such setups, the transformer ensures incoming AC voltage being fed to the VFD is ‘clean’ before undergoing AC-to-DC conversion (more on this later).

An isolation transformer that is used for this purpose typically has the same primary and secondary voltage (for instance, 480V single-phase to 480V single-phase), in the following equipment setup:

Supply Line => Isolation Transformer => VFD => Motor

 

Sizing Transformers for VFD Applications

Determining the size of a transformer for VFD loads is a straightforward process. To start, individuals must select an appropriate kVA rating for the isolation transformer, sized to handle the VFD’s continuous input amps. At this stage, it is important to consider that you do not have to oversize the unit for the VFD, since the transformer already has current overload protection.

Keeping that in mind, the next step is to convert the continuous input amp requirements of the VFD to kVA:

kVA = 1.732 x Line-to-Line Voltage x VFD Input Amps / 1,000

*Note: The 1.732 multiplier, which is the square root of 3 [√3], is for three-phase kVA.

Example: Line-to-line voltage = 240V AC, VFD input amps = 240A

kVA = 1.732 x 240V x 240A / 1,000

kVA = 99,763.2 / 1,000

kVA = 99.8 or 100 kVA (rounded up)

For single-phase kVA computations, remove the 1.732 multiplier:

kVA = Line-to-Line Voltage x VFD Input Amps / 1,000

kVA = 240V x 240A / 1,000

kVA = 57,600 / 1,000

kVA = 57.6 or 75 kVA (rounded up)

After determining the appropriate kVA rating of the transformer, individuals should also double-check the primary and secondary voltages for compatibility. The primary voltage of the unit must match the input/supply line; while the secondary voltage must match the input requirements of the connected VFD.

 

Mitigating Harmonics

VFDs can contribute to harmonic distortion, which is defined as electrical pollution due to deviation from a pure sinusoidal wave form to a non-sinusoidal wave form. Harmonic currents consist of greater (odd or even) multiples of the fundamental, sinusoidal wave form. For example, the 5th harmonic of a 60 Hz network is 300 Hz. Even harmonic currents contribute to less machine performance issues, than odd harmonic currents.

The presence of harmonic currents is a concern for VFDs, because the units generate non-linear loads. When visually presented, the waveform of a non-linear load appears random and staggered. It is important to highlight that harmonics are only an issue when the amount of current exceeds certain limits or thresholds.

Since harmonic currents are considered to be unusable, the energy is converted to heat. This is one of the main negative effects of harmonic currents. Other crippling effects associated with harmonics include the following:

  • Vibration
  • Noise (humming)
  • Malfunction due to distorted voltage
  • Premature equipment failure
  • Flickering (for lights and displays)
  • Capacitator performance
  • Generation of false readings (for meters)

 

Isolation transformers can be used to decrease the creation of harmonic currents, by rectifying input current from the supply line to the VFD. For protection against unwanted electrical disturbances, the unit’s primary and secondary windings may be covered with an electrostatic shield.

Alternatively, it would also be possible to use multi-pulse drives (12, 18 or 24-pulse), trap filters and broadband filters to decrease harmonic distortion, when using VFDs. ANSI/IEEE Standard 519 and IEEE C57.110 provide recommendations for mitigating harmonic currents in industrial facilities.

 

Subscribe To Our Newsletter

Keep up with Larson Electronics new products, discount codes & latest news!

  • This field is for validation purposes and should be left unchanged.
100% Privacy.

Recent Posts

Stop the Spread of COVID-19 Corona Virus on Mobile Devices

Larson Electronics UV Tablet Box Nowadays, numerous businesses rely on mobile devices, including tablets, phones and digital pads, during operations....

Purchase and Rent Out UV Light Carts to Fight COVID-19 Corona Virus

Larson Electronics UV Light Carts – Rental Companies Rental companies, or businesses that offer equipment for rent or temporary use,...

Sanitize Personal Devices Quickly with UV Disinfection Boxes and Lights

Larson Electronics Desktop UV Sanitation Light Setup a designated sanitation area for personal devices to disinfect the COVID-19 corona virus...

Dual Recessed Troffer UV Disinfection Lights for Corona Virus

Larson Electronics UV Troffer Disinfection Lights What if, with the flip of a switch, you could eliminate corona virus from...

Keep COVID-19 Essential Businesses Running with Buck-boost Transformers

Larson Electronics Buck Boost Transformers – Corona Virus Essential businesses experiencing power issues must address the problem themselves, as a...