LA200-P by LEM USA Inc. Datasheet | DigiKey

LA200-P Datasheet by LEM USA Inc.

Page 1/3
9April2013/version 16 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
N° 90.09.44.000.0
IPN = 200 A
Features
Closed loop (compensated)
current transducer using the Hall
effect
Insulating plastic case recognized
according to UL 94-V0.
Advantages
Excellent accuracy
Very good linearity
Low temperature drift
Optimized response time
Wide frequency bandwidth
No insertion losses
High immunity to external
interference
Current overload capability.
Applications
AC variable speed drives and
servo motor drives
Static converters for DC motor
drives
Battery supplied applications
Uninterruptible Power Supplies
(UPS)
Switched Mode Power Supplies
(SMPS)
Power supplies for welding
applications.
Application domain
● Industrial.
Current Transducer LA 200-P
For the electronic measurement of currents: DC, AC, pulsed...,
with galvanic separation between the primary circuit and the secondary
circuit.
Electrical data
IPN Primary nominal current rms 200 A
IPM Primary current, measuring range 0 .. ± 300 A
RM Measuring resistance @ TA = 70°C TA = 85°C
RM min RM max RM min RM max
with ± 12 V @ ± 200 A max 0 30 0 26
@ ± 250 A max 0 8 0 4
with ± 15 V @ ± 200 A max 0 60 0 56
@ ± 300 A max 0 12 0 8
ISN Secondary nominal current rms 100 mA
KN Conversion ratio 1 : 2000
UC Supply voltage (± 5 %) ± 12 .. 15 V
IC Current consumption 16 (@ ± 15 V) + IS mA
Accuracy - Dynamic performance data
X Accuracy @ IPN, TA = 25°C @ ± 15 V (± 5 %) ± 0.40 %
@ ± 12 .. 15 V (± 5 %) ± 0.65 %
εL Linearity error < 0.15 %
Typ Max
IO Offset current @ IP = 0, TA = 25°C ± 0.20 mA
IOM Magnetic offset current 1) @ IP = 0 and specified RM,
after an overload of 3 x IPN ± 0.25 mA
IOT Temperature variation of IO 0°C .. + 70°C ± 0.10 ± 0.25 mA
- 40°C .. + 85°C ± 0.15 ± 0.55 mA
tra Reaction time < 500 ns
tr Step response time 2) 3) to 90 % of IPN < 1 µs
di/dt di/dt accurately followed 3) > 200 A/µs
BW Frequency bandwidth (- 1 dB) DC .. 100 kHz
General data
TA Ambient operating temperature - 40 .. + 85 °C
TS Ambient storage temperature - 40 .. + 90 °C
RS Secondary coil resistance @ TA = 70°C 76
 TA = 85°C 80
m Mass 40 g
Standard EN 50178: 1997
Notes: 1) The result of the coercive field of the magnetic circuit
2) With a di/dt of 100 A/µs
3) The primary conductor is best filling the through-hole and/or the return of
the primary conductor is above the top of the transducer.
16044
dc dc. 0w
Page 2/3
9April2013/version 16 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Current Transducer LA 200-P
Isolation characteristics
Ud Rms voltage for AC insulation test, 50 Hz, 1 min 3 kV
ÛW Impulse withstand voltage 1.2/50 µs 7 kV
Ue Partial discharge extinction voltage rms @ 10 pc > 1.8 kV
Min
dCp Creepage distance 6.7 mm
dCI Clearance 6.7 mm
CTI Comparative Tracking Index (group IIIa) 175
Applications examples
According to EN 50178 and IEC 61010-1 standards and following conditions:
Over voltage category OV 3
Pollution degree PD2
Non-uniform field
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
EN 50178 IEC 61010-1
d
Cp
, d
CI
, Û
W
Rated insulation voltage Nominal voltage
Basic insulation 600 V 600 V
Reinforced insulation 300 V 300 V
= 1.0.61. = * 2x¢17§><45 __="" 4;="" i="" x="" m="" ‘="" j="" el="" el="" “0-="" ‘="" \="">< :-="" \="" \1)="" ‘="" m="" m="" ‘="" n="" r.="" \="" v="" \="" ,="" m="" z="" ‘="" ‘="" w="" w="" \="" w="" ‘="" x="" 41.4="" 336="" 3‘“?="" 291="" [‘7="" ‘3="=" mm="" ,’="" flgn'u'xrs="" :fl="" freppuqs="" :rp="" ®="" m’="" 57w="" 6.7="" m="" ‘="" ‘="" nm="" ‘="" n="" ll,="" 6="" n="" \="" m="" “="" g="" a="" w="" e="" m="" “f="" x="" x="" x="" 4”="" w="" v="" v="" w="" n="" oul="" 1'5="" ‘="" 12.7="" ’27="" 5.05="" 7="" 7="" rut="" kc="" 1.81.="">
Page 3/3
9April2013/version 16 LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice www.lem.com
Dimensions LA 200-P (in mm)
Mechanical characteristics
General tolerance ± 0.2 mm
Primary through-hole 17 x 11 mm
Fastening & connection of secondary 4 pins
0.63 x 0.56 mm
Recommended PCB hole 0.9 mm
Supplementary fastening 2 holes Ø 1.75 mm
Recommended PCB hole 2.4 mm
Recommended screws PT KA 22 x 6
Recommended fastening torque 0.5 N·m
Remarks
IS is positive when IP flows in the direction of the arrow.
Temperature of the primary conductor should not exceed
100°C.
Dynamic performances (di/dt and response time) are
best with a single bar completely filling the primary hole.
This is a standard model. For different versions (supply
voltages, turns ratios, unidirectional measurements...),
please contact us.
Connection
IS
IP