Below is a snapshot of the Web page as it appeared on 4/9/2024 (the last time our crawler visited it). This is the version of the page that was used for ranking your search results. The page may have changed since we last cached it. To see what might have changed (without the highlights), go to the current page.
Bing is not responsible for the content of this page.
Current Transducer FA-050 .. 100PV
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 50 .. 100 A
Electrical data
Primary nominal DC current Primary current measuring range Type
IPN (A)
50 100
IP (A)
0 .. ± 70 More View
0 .. ± 130 FA - 050PV FA - 050PV FA - 100PV FA - 100PV
VOUT IC VC Vd
Output voltage @ ± IPN , RL = 10 kΩ , T A = 25°C ± 4 Current consumpution 16 + IPN /1000
Features
V mA V kV
±4 16+ IPN /2000 ± 15 2.5
Supply voltage (± 5 %) R.m.s. voltage for AC isolation test, AC50/60Hz, 1 min
• Hall effect measuring principle • PC Board Mount Type • Low power consumption • Extended measuring range (3 x IPN ) • Galvanic isolation between Primary • Isolation voltage 2000V
and Secondary circuit
Accuracy-Dynamic performance data
ε
X
L
VOE VOH VOT TCε G tr f
Accuracy @ T A = 25°C, @ ± 15V (± 5%) Linearity (0 .. ± IPN ) Electrical offset voltage, T A = 25°C Hysteresis offset voltage @ IP = 0, after an excursion of 1 x IPN Thermal drift of VOE Thermal drift of the gain (% of reading) Response time @ 90% of IP Frequency bandwidth (- 1 dB)
< ± 1.5 @IPN < ± 0.25 ± 0.016 < ± 0.012 < ± 0.04 < ± 0.1 <1 DC .. 100
% % V V mV/°C %/°C µs kHz
Advantages
• Easy Mounting • Small size and space saving • Only one design for wide current • High immunity to external inteference
ratings range
Applications
General data
TA TS m Ambient operating temperature Ambient storage temperature Mass - 10 .. + 70 - 15 .. + 80 25 °C °C g
• DC motor drives • Switched Mode Power Supplies • AC variable speed drives • Uninterruptible Power Supplies • Battery supplied applications • Power supplies for welding
applications. (UPS) (SMPS)
010301/1 www.nanalem.co.jp
FA- 050 .. 100PV
Terminal Pin Identification
UNIT: mm
NANALEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.